Specified System Performance Standard and IMS detail

 

Empty space, drag to resize
Specified System SS Performance Standard IMR Procedure
SS1 — Automatic systems for fire suppression NZS4541:2013 — Automatic Fire Sprinkler Systems  NZS4541:2013 — Automatic Fire Sprinkler Systems (Part 12)
SS2 — Automatic or manual emergency warning systems for fire or other dangersNZS4512:2021 — Fire detection and alarm systems in buildingsNZS4512:2021 — Fire detection and alarm systems in buildings (Part 6)
SS3/1 — Electromagnetic or automatic doors or windows - Automatic Opening DoorsNZS4239:1993 — Automatic sliding door assembliesNZS4239:1993 — Automatic sliding door assemblies (Appendix A)
SS3/2 — Electromagnetic or automatic doors or windows - Access Controlled DoorsC/AS2 (November 2020) Section 3.15.2 & 3.15.7Specific inspection, maintenance and reporting procedures from the designer
SS3/3 — Electromagnetic or automatic doors or windows - Interfaced Fire/Smoke DoorsC/AS2 (November 2020) Section 3.15.9 & 3.15.10AS4178:1994 — Electromagnetic door holders
SS4 — Emergency LightingAS2293.1:2005 — The use of ventilation and air conditioning in buildings - Part 1 System design, installation and operationAS/NZS2293.2:1995 — Emergency evacuation lighting for buildings - Part 2 Inspection and maintenance
SS5 — Escape Route Pressurisation SystemsAS1668.1:2015 — The use of ventilation and air conditioning in buildingsAS1851.6:2012 — Routine service of fire protection systems and equipment
SS6 — Riser Mains for Use by Fire ServicesNZS4510:2008 — Fire hydrant systems for buildingsNZS4510:2008 — Fire hydrant systems for buildings (Section 9)
SS7 — Automatic Backflow Preventers connected to a Potable Water SupplyAS/NZS2845.1:2010 — Water supply Backflow prevention devices Part 1 Materials, design and performance requirementsNZ Backflow Testing Standard 2011
SS8/1 — Lifts, Escalators, Travellators or other systems for moving people or goods within buildings - Passenger Carrying LiftsNZS4332:1997 — Non-domestic passengerNZS4332:1997 — Non-domestic passenger and goods lifts (Part 4)
SS8/2 — Lifts, Escalators, Travellators or other systems for moving people or goods within buildings - Service LiftsNZS4334:2012 — Platform lifts and low-speed liftsNZS4334:2012 — Platform lifts and low-speed lifts (Appendix A)
SS8/3 — Lifts, Escalators, Travellators or other systems for moving people or goods within buildings - Escalators etc.EN115.1:2008 — Safety escalators and moving walks - Construction and installationSpecific inspection, maintenance and reporting procedures from the designer
SS9 — Mechanical ventilation or air conditioning systemsNZS4303:1990 —  Ventilation for acceptable air quality AS1668.2:2002 - The use of ventilation and air conditioning in buildings - Part 2: Mechanical ventilation in buildingsAS/NZS3666.2:2011 — Air-handling and water systems of buildings - Microbial Control Part 2: Operation and maintenance
SS10 — Building maintenance units providing access to exterior and interior walls of buildingsBS6037.2:2004 — Code of practice for the planning, design, installation and use of permanently installed access equipment. Travelling laddies and gantriesBS6037.2:2004 — Code of practice for the planning, design, installation and use of permanently installed access equipment. Travelling laddies and gantries
S11 — Laboratory fume cupboardsAS/NZS2243.8:2014 — Safety in laboratories part 8. Fume cupboardsASNZS2243.8:2014 — Safety in laboratories part 8. Fume cupboards (Section 5.5)
SS12/1 — Audio Loops or Other Assistive Listening SystemsAS60118.4:2007 — Hearing aids - Magnetic field strength in audio-frequency induction loops for hearing aid purposeAS60118.4:2007 — Hearing aids - Magnetic field strength in audio-frequency induction loops for hearing aid purpose
SS12/2 — Audio Loops or Other Assistive Listening Systems - FM or Infrared beam transmission systemSpecific designSpecific design
SS13/1 — Smoke Control Systems - MechanicalAS1668.1:2015 — The use of ventilation and air conditioning in buildingsAS1851:2015 — Routine services of fire protection systems and equipment (Section 13)
SS13/2 — Smoke Control Systems - Natural Smoke ControlSpecific designAS1851:2015 — Routine services of fire protection systems and equipment (Section 13)
SS13/3 — Smoke Control Systems - Smoke CurtainsBS EN120101:2005 — Smoke and heat control systems. Specification for smoke barriersAS1851:2015 — Routine services of fire protection systems and equipment (Section 9)
SS14/1 — Emergency power systems for, or signs relating to, a specified system in any of specified systems 1-13 - Emergency Power SystemsNZS6104:1981 — Specification for emergency electricity supply in buildingsNZS6104:1981 — Specification for emergency electricity supply in buildings
SS14/2 — Emergency power systems for, or signs relating to, a specified systems 1-13 - SignsSS02 — F8/AS1 ( January 2017) Section 5.1
SS03/1 — F8.3.1 (April 2012)
SS03/02 — F8.3.1 (April 2012)
SS03/3 —  F8/AS1 (January 2017) Section 5.2
SS06 — F8/AS1 (January 2017) Section 5.5
SS08/1 — F8/AS1 (January 2017) Section 5.3
SS12/1 — F8/AS1 (January 2017) Section 6.3
A.  Of the correct type
B.  Present and in the right locations
C.  Legible
SS15/1 — Other Fire Safety Systems or Features - Systems for Communicating Spoken Information Intended to Facilitate EvacuationNZS4512:2012 — Fire detection and alarm systems in buildingsNZS4512:2012 — Fire detection and alarm systems in buildings (Part 6)
SS15/2 — Other Fire Safety Systems or Features - Final ExitsC/AS2 (November 2020) Sections 3.12 & 3.15Final exits should be inspected to ensure they can be opened and are not:
A.  Locked
B.  Barred
C.  Blocked

And that door locking devices:
A.  Are clearly visible
B.  Are easily operated without a key or other security devices
C.  Do not prevent or override the direct operation of panic bolts fitted to any door
SS15/3 — Other Fire Safety Systems or Features - Fire SeparationsFor walls, floors and ceilings: Structural adequacy/integrity/insulation C/AS2 (November 2020) Sections 2.3 & 4

For fire doors: NZS4520:2012 Fire resistant door sets.
For walls, floors and ceilings:
A.  Separation are not damaged or deteriorated in a way that could adversely affect their fire resistance function
B.  Separations do not have new penetrations without suitable fire-stopping

For fire doors: NZS4520:2012 Fire resistant door sets (Section 7)
SS15/4 — Other Fire Safety Systems or Features - Evacuation SignsIlluminated signs
F8/AS1 (January 2017) Section 4

Photoluminescent Signs
F8/AS1 (January 2017) Section 4.5.4
Illuminated signs should be inspected to ensure they are:
A.  Of the correct type
B.  Present and in the right locations
C.  Legible
D. Illuminated
S15/5 — Other Fire Safety Systems or Features - Smoke SeparationsSmoke Control Doors — C/AS2 (November 2020) Appendix C, Section C6.1

Smoke Separations — C/AS2 (November 2020) Definitions
For walls, floors and ceilings:
A.  Separations are not damaged or deteriorated in a way that could adversely affect their fire resistance function
B.  Separations do not have new penetrations without suitable fire-stopping

Smoke doors are not:
A.  Locked
B.  Barred
C. Blocked
SS16 — Cable CarsNZS5270:2005 — Cable cars for private residences - design, construction, installation and maintenanceNZS5270:2005 — Cable cars for private residences - design, construction, installation and maintenance